Acceptable fluid |
Application |
Nominal size (mm) |
Flow rate range (m/s) |
Flow rate accuracy |
Level range (m) |
Level accuracy |
Operating temperature (°C) |
Max operating pressure (Bar) |
ATEX approval |
| 3300/3500 |
Liquid |
Open channel or closed pipe |
N/a |
0.03 - 4 |
±1% (<3m/s) ±1.5% (>3m/s) |
0 – 4; 0- 10 |
±1% in flow stream |
|
10 bar @ 25°C |
No |
| Precision 190P/190PLT |
Liquid |
Closed pipe |
15 – 1200 or 1200 – 6500 (190P) 15 – 300 (190PLT) |
0.01 – 25 (higher by request) |
±1-2% or ±0.02 m/sec whichever is greater |
N/a |
N/a |
-30 to 105 |
|
No |
| Precision 190F |
Liquid |
Closed pipe |
25 – 500; 500 – 1200; 1200 – 6500 |
0.01 – 25 (higher by request) |
±1-2% or ±0.02 m/sec whichever is greater |
N/a |
N/a |
-30 to 105 |
|
No |
| OCM III |
Liquid |
Open channel |
N/a |
|
|
0.3 - 1.2; 0.6 - 3 |
<0.02% |
|
|
No |
| ULTRA Eggs |
Liquid |
Closed pipe |
15 |
3 – 70 (l/min) |
±3% (±1% option) |
N/a |
N/a |
-20 to +60 |
7 |
No |