Pointek CLS 200 is a versatile inverse frequency shift capacitance level switch with optional rod/cable choices and configurable output, ideal for detection of liquids, solids, slurries, foam, and interfaces. The digital version (with optional PROFIBUS PA) includes a display and provides additional diagnostic features.
The Pointek CLS 200 is offered in standard and digital versions. The standard version has 3 LED indicators with basic relay and solid-state switch alarms. The digital version provides an integral LCD display for standalone use, and provides PROFIBUS PA communication (profile version 3.0, Class B) when required.
The power supply is galvanically isolated and accepts a wide range of voltages (12 to 250 V AC/DC for standard version and 9 to 32 V DC for digital version). The stainless steel and PPS (PVDF optional) materials used in the probe construction provides a temperature rating up to +125°C on the process wetted portion of the probe. The switch responds to any material with a dielectric constant of 1.5 or more by detecting a change in oscillating frequency, and it can be set to detect before contact or on contact with the probe. The CLS 200 operates independently of the tank wall or pipe, so it does not require an external reference electrode for level detection in a non-conductive vessel such as concrete or plastic.
Modular design and construction provide a wide choice of configurations, including rod, cable and sanitary versions. When used with a SensGuard protection cover, the CLS 200 is protected from shearing, impact, and abrasion in tough primary processes.
Features of the Pointek CLS 200 include:
- Potted construction protects signal circuit from shock, vibration, humidity and/or condensation.
- High chemical resistance
- Level detection independent of tank or pipe earth reference
- Insensitive to product buildup due to high frequency oscillation (5.5 MHz)
- High sensitivity allows installation in a wide range of liquids, solids, or slurry applications.
- Integral LCD display allows for easy setup of CLS 200 when you can configure switching threshold, even under the most demanding process conditions.
- Extended rod, cable, and sanitary versions available
- Standard version: 3 LED indicators for adjustment control, output status and power
- Digital version: integral LCD display, and optional PROFIBUS PA communication
General Applications of the Pointek CLS 200:
- Liquids
- Slurries
- Powders
- Granules
- Food and Pharmaceuticals
- Chemicals
- Hazardous areas
Specs
Contact Us Today To Enquire About Our Products And Services
Product Specification
The Pointek CLS 200 is a versatile inverse frequency shift capacitance level switch. It has optional rod/cable choices and configurable output, ideal for detection of liquids, solids, slurries, foam, and interfaces.
Specification Detail of the Capacitance Level Switch Pointek CLS 200:
Probe Length
5500mm (cable version 30000mm)
Material Body
Epoxy coated aluminium.
Flow Range
N/A
Accuracy
N/A
Operating Temp Range
-40 to 125°C
Pressure Range
-1 … to +10bar G
Outputs & Comms
Relay/solid-state
Insertion / Inline
Insertion
Fluid Type
Liquid and solids
Applicable Liquids
liquids, slurries, powders, granules, food and pharmaceuticals, chemicals, hazardous areas
Power
12-250V AC/DC 0 … 60 Hz max 2 W
Approvals
CE, CSA, FM, C-TICK, ATEX II, WHG VLAREM II
Connection Type
¾” NPT [(Taper), ANSI/ASME B1.20.1] R 1″
[(BSPT), EN 10226/PT (JIS-T), JIS B 0203] G 1″ [(BSPP), EN ISO 228-1/ PF (JIS-P), JIS B 0202]