The Pointek CLS 300 is an inverse frequency shift capacitance level switch with optional rod/cable choices and configurable output. It is ideal for detecting liquids, solids, slurries, foam, and interfaces in demanding conditions where high pressure and temperatures are present. The Digital version (with optional PROFIBUS PA) includes a display and provides additional diagnostic features.
The Pointek CLS 300 is offered in standard and digital versions. The standard version has 3 LED indicators with basic relay or solid-state switch alarms. The digital version provides an integral LCD display for standalone use, with PROFIBUS PA communication (Profile version 3.0, Class B) when required. Solid-state switch alarm is standard. The robust design of CLS 300 makes it specifically applicable for heavy solids applications where abrasive materials occur like the mining industry. The fully potted electronics are unaffected by condensation, dust, or vibration. Wetted parts are made of stainless steel with a PFA shield for high chemical resistance. Ceramic inserts are supplied with high temperature CLS 300 devices. Materials with low or high dielectric constants can be accurately detected. The unique active shield suppresses interference from material build-up.
The unique modular design of the Pointek CLS 300 provides a wide range of configurations, process connections, extensions, and approvals to meet the temperature and pressure requirements of specific applications. The modular design makes ordering easier and reduces stocking requirements. A wide range of probe configurations is available, including rod and cable versions.
Inverse Frequency Shift Capacitance Level Switch for Demanding Conditions including Low/High Pressure, High Temperature, Corrosive and Abrasive Materials. Inverse frequency shift capacitance level switch with optional rod/cable choices and configurable output. It is ideal for detecting liquids, solids, slurries, foam, and interfaces in demanding conditions where high pressure and temperatures are present; digital version (with optional PROFIBUS PA) includes a display and provides additional diagnostic features.
Features of the Pointek CLS 300 include:
- Patented Active-Shield technology so measurement is unaffected by material build-up in active shield section.
- Performs in extremely abrasive conditions because of solid rod construction.
- Standard version: 3 LED indicators for adjustment control, output status and power
- Digital version: integral LCD display, and optional PROFIBUS PA communication
- Push-button calibration, full-function diagnostics
- Multiple output options
General Applications of the Pointek CLS 300:
- Liquids
- Slurries
- Bulk solids
- Relatively high pressure and temperature
- Hazardous areas
- Milling and Mining applications
Specs
Contact Us Today To Enquire About Our Products And Services
Product Specification
The Pointek CLS 300 is an inverse frequency shift capacitance level switch with optional rod/cable choices and configurable output.
Specification Detail of the Capacitance Level Switch Pointek CLS 300:
Probe Length
250mm to 25000mm
Material Body
Powder coated aluminium.
Flow Range
N/A
Accuracy
1% change in actual captaincy
Operating Temp Range
-40 to 400°C
Pressure Range
-1 … to +35bar G
Outputs & Comms
Relay/solid-state
Insertion / Inline
Insertion
Fluid Type
Liquid and solids
Applicable Liquids
liquids, slurries, bulk solids
Power
12-250V AC/DC 0 … 60 Hz max 2 W
Approvals
CE, CSA, FM, C-TICK, ATEX II, WHG
Connection Type
Threaded – ¾” to 1½” NPT/G/RWelded flange – 1″ to 4″ ASME or DN25 to DN100