  • Polypropylene enclosure
  • Hazardous applications
  • Easy set-up w/ LED indicators

Switch-Pro Level Controller

Switch-Pro Remote Level Controller available in CSA approved, general purpose (LC4X) or isolation (LC9X) versions with built-in intrinsic safety barriers for use with associated apparatus, the level controller is offered in three configurations for pump and valve control.

  • LC40/90 accepts one level sensor input and provides one 10A relay.
  • LC41 accepts two level sensor inputs and provides one latching 10A relay for automatic fill or empty control.
  • LC42/92 accepts three level sensor inputs with one latching 10A relay output for automatic fill or empty control, and a second non-latching 10A relay for high level alarm or low-level alarm.

The optional NEMA 4X polycarbonate enclosure is a great choice for field mount installations and comes complete with a DIN rail mounting kit.

Features of the Switch-Pro Remote Level Controller include:

  • ​LED indicators provide user with power, sensor and relay status.
  • Fail-safe relay control of pumps and valves with 0-60 second time delay
  • PP 35 mm DIN enclosure with removable terminal strips
  • Contact type: (2) SPDT relays
  • Sensor inputs: (1-3) level switches
  • Enclosure rating: None
  • Enclosure mount: 35mm DIN rail

Ordering More Than Five?: If you require five or more units, contact our sales team for a quote.

Specs

Manufacturer: Flowline

Contact Us Today To Enquire About Our Products And Services


Product Specification

The Switch-Pro Remote Level Controller is offered in three versions with 1 or 2 relays and 1-3 sensor inputs.

 

Specification Detail of the Switch-Pro Remote Level Controller:


LED Indication Sensor

Power & relay

Enclosure Material

PP, UL94VO

Consumption

5 watts max

Sensor Inputs

Up to 3 level switches

Operating Temp Range

-40° to 60°C

Sensor Supply

13.5 VDC @ 27 mA

Contact Output

Selectable NO / NC

Contact Rating

250 VAC @ 10A

​​Contact Delay

0-60 seconds

Enclosure Type

35m DIN rail

Supply Voltage

120 / 240 VAC, 50-60 Hz

Approvals

CE

Classification

General Purpose